Seitenansicht 3
Air Circuit Breakers ME10
4
Reference guide - October 2014
Series ME10
The new serie ME10 has been designed as a Modern ‘Power
Circuit Breaker without neglecting its AEG’s heritage of more
than 50 years in building Air Circuit Breakers.
The ME10 range of Power Circuit breakers encompasses a line
of 3 and 4 pole Air Circuit Breakers with Nominal Currents ranging
from 400 to 6400Amp in four basic envelopes. (see diagram).
One of the most important user parameters is not the nominal
rating of an ‘Air Circuit Breakerin free air but its current Rating
within a panel or enclosure.
Breakers ‘enclosed ratings’ are determined by the heat dissipation
produced by the device and its ability to carry current at the
temperature within the enclosure.
ME10 Power Circuit breakers have been designed with low
Power dissipation values and allow relatively high currents at
high ambient temperatures.
The serie ME10 has been designed to offer an uncompromising combination of a fast
interruption at high fault levels attaining values of 40 Milliseconds or less whilst maintaining
selectivity. The electronic trip unit, already in its basic model, is equipped with protection
channels for overload and short-circuit with delay adjustment intervention, in a wide range
of bands of time
Optionally a full network measurement device can be installed on the device. Relays can
be included to trip the breaker on Voltage Unbalance, Current Unbalance, Power reversal
etc. The device can be equipped with
Communication for use with the Modbus
or Profibus protocol whilst events as
Overload, Short-circuit and Groundfaults
can be tracked, the RELT function to
protect Service Personnel against the
hazards of Short Circuits.
Independent of the number of poles,
rated current or interruption rating, each of the two patterns has a
common height, depth and cut-out dimension.
This strongly simplifying the design of panels and equipment in
which these devices are used.
The basic breaker width has been optimized to allow for space
to connect in- and outgoing bus bars and cables. Both Fixed
and Draw-out Power Circuit Breaker types are supplied with rear
connections suitable for Rear Access Horizontal busbar connection.
A large range of internal accessories as Electrical Operators, up to four Shunt
Releases, Closing Coils or Undervoltage releases, Interlock Coils, Auxiliary and
Alarm contacts, Carriage switches, Coil indication contacts and Breaker status
switches are available.
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
Serie T
1600A
Icu=Ics
R
K
S
N
Serie 1
2000A
Icu=Ics
Serie 3
6400A
Icu=Ics
Serie 2
4000A
Icu=Ics
kA
M
G
Seitenansicht 3