Air Circuit Breakers ME10
13
Reference guide - October 2014
Electronic Trip Units
LT protection
ST protection
I protection
RELT
Measurement
1
Diagnostic
Input/Output
Protezioni con relè
GF protection
ZSI
Modbus
Canale I extended
Profibus
I extended protection
Profibus
GT-Rating Plug
GT Trip Unit
with no protection
Description
Overload current setting Ir=0,2… 1In
Class C 0,5... 40
Fuse typetime bands available
Inverse time current curve
Neutral protection (50%-63%-100%)
Thermal memory
Short-circuit setting 1,5… 12Ir
Possibility to Switch
Time delay adjustable 30... 940ms
I
2
t protection time bands available
Istantaneous short circuit setting 2… 15Ie
Selective execution
Fixed istantaneous or HSOC protection
Istantaneous 40ms
Current L1, L2, L3
Voltage L1, L2, L3
Energy (kWh)
Real, apparent, reactive, total power
Peak and demand power
Frequency
Trip reason indication
Trip info (Magnitude/Phase)
Waveform capture
Trip counter
Relay basedon current level
Good and Bad health indicator
Event logger
Watchdog
2 electronic inputs
2 general relay outputs
Voltage unbalance
Undervoltage
Overvoltage
Current unbalance
Power reversal
Available GF-sum or GF-ct (ground return)
Ground fault setting 0,1… 1In
Time delay adjustable 30... 840ms
I
2
t protection time bands available
Zone selective interlock
Modbus communication
Istantaneous short circuit setting 2… 30Ie
Profibus communication (to replace the modbus)
Istantaneous short circuit setting 2… 30Ie
Profibus communication (to replace the modbus)
(required for all types)
(for Non-automatic types)
Catalogue
number
GTG00N5T8SR
GTG00N7T8SR
GTG00N5T9SR
GTG00N7T9SR
GTPUNI
G3G00KA-SR
Reference
number
408849
408851
408853
408855
408860
408796
GT-H
+
+
+