12
Power factor range 0.3 lag. to 0.9 cap.
at full output
Power reduction of 20 % to 0.5 cap.
Inverter frequency 40 % power reduction
(Bypass disabled, Input Frequency Range
40 - 70 Hz)
Sinus waveform Sinus waveform distortion
<3 % THD (linear load)
<5 % THD (non-linear load)
Connection IEC sockets
Crest factor 3:1
Overload behaviour up to 105 % continuous;
>105 % – <110 % for 60 s;
≥110 % – <125 % for 30 s;
≥125 % – 150 % for 10 s;
Then automatic inverter to Bypass
in < 4 ms (switches back when
overload damps = Load < 90%)
Overload bypass Up to 125 % continuous
>125 % – 150 % 10 min.
Short circuit 3 x I
N
for 100 ms
Battery
Autonomy Time
External
battery module
cos = 0.8 lag. / 100 % charged battery
C.1000 C.2000 C.3000
With integrated battery 4.5 min. 7 min. 3.5 min.
1 add. battery module 25 min. 38,5 min. 21 min.
2 add. battery modules 51 min. 70 min. 45 min.
Battery check
(programmable)
daily; weekly; monthly
Rated DC voltage (intermediate circuit)
Protect C.1000 36 VDC
Protect C.2000 96 VDC
Protect C.3000 96 VDC
Battery charging current
(max.)
1 ADC