1OPERATING INSTRUCTIONS UPSPROTECT B. PROTECT B. 750PROTECT B. 1000PROTECT B. 1500PROTECT B. 2000PROTECT B. 3000
103 Safety3.1 General Safety InstructionsRead these operating instructions carefully prior to commissioning of the PROTECT B. UPS and obs
11The output may be live, even if the UPS is not connected to the mains supply, as the UPS has its own internal power supply (battery)!For heal
12♦ Never connect the mains input to the UPS output.♦ Ensure that no fluids or foreign bodies can penetrate the UPS!♦ Do not block the air vents of th
13Danger! Explosive!Never throw batteries into open fire. Never open or damage batteries. (Electrolyte may leak out and damage skin and eyes. It
143.3 Certification
153.4 Technical DataModel power PROTECT B. 750 750 VA / 500 WPROTECT B. 1000 1000 VA / 700 WPROTECT B. 1500 1500 VA / 1050 WPROTECT B. 2000 2000 VA /
16Output current power (at 230 Vac)PROTECT B. 750 3.2 APROTECT B. 1000 4.3 APROTECT B. 1500 6.5 APROTECT B. 2000 8.7 A PROTECT B. 3000 13 A Transfer t
17Recharge time 3 h (UPS in (to 90 % of rated capacity) standard configuration)7 h (UPS with 1 add. batterypack)12 h (UPS with 2 add. battery packs)1
18Number of outletsPROTECT B. 750 4 x IEC 320PROTECT B. 1000 6 x IEC 320PROTECT B. 1500 6 x IEC 320 (sep. module)PROTECT B. 2000 6 x IEC 320 (sep. mod
19GuidelinesThe PROTECT B. complies with the product norm EN 50091.The CE symbol on the unit certifies the compliance to the EG guidelines for 73/23 E
2Thank you for purchasing a PROTECT B. UPS fromAEG Power Solutions. The following security advices are an important component of the manu
204 Set-Up and Operation4.1 Unpacking and InspectionThe unit has been fully tested and inspected. Although the unit has been packed and shipped with t
21Please keep the plastic packaging bags away from babies and children in order to safeguard against suffocation accidents.Handle the c
224.3 Connections, Operation / Display Elements4.3.1 Front view:Model designationwith type rating detailsPROTECT B.750 and B.1000Model designationwith
234.3.2 Operating panelExplanations (see also chapter 6)1. Main switch of the UPS (mains switch)2. Pushbutton for system test (manually triggering) or
244.3.3 Rear view (connections):Comments:1. Mains connection (UPS input) with electric fuse and integrated spare fuse2. Load connections (UPS outputs)
25Comments:1. Mains connection (UPS input)2. Load connections (UPS outputs)PROTECT B. 3000 with additional load connection(IEC 320-16A)3. Surge protec
265 Commissioning5.1 DeploymentThe UPS was constructed for both horizontal / flat (rack/19") operation and vertical / standing (tower) operation.
27When operating the system with more than one battery module, the UPS can be positioned between the modules. The following graphic di
285.1.2 19" Rack Mount SetupROTECT B. 750, 1000, 1500, 2000 and 3000 can be installed in 19” racks. The UPS and external battery enclosure need 2
294. Add up the front panels for both sides. The mechanical installation of the UPS is completed now.PROTECT B. 1500 und B. 2000This model i
31 Notes on these Operating InstructionsDuty to Provide InformationThese operating instructions will help you to install and operate the Uni
301. Place the UPS on a flat and in a clean place that the front side of the UPS is facing to you. 2. Loosen the screws in the middle of the
316. Align the second (smaller) mounting bracket at the rear of both units and mount them with the enclosed screws. 7. Install Plug of the battery
32PROTECT B. 3000 / B. 3000 BPFor mounting the 3000 VA UPS in a 19” rack fix the mounting ears to the UPS and install the unit to the rails. Do the sa
33PROTECT B. 3000Connect the supplied battery module cable from extended battery module to the external battery port of the rear of UPS.If cont
347. Activate the external EPO switch to test the EPO function8. De-activate the external EPO switch and restart the UPS.5.4 Electric sta
35operating stag has been reached (pos. 7 p. 3).In case anything different occurs, please follow the instructions in Chapters 6.2 / 6.3.iPlease s
366. After selecting the mode, press the confirmation buttonmore than three seconds to complete the configuation.5.5 OperationOnce you have connect
37If the UPS does not automatically return to normal operation after a few minutes, close all jobs as usual and switch off your loads (e.g. PC) bef
38Also avoid short-term unit overloads, which may, for example, occur when connecting a laser printer or laser fax machine. Do not connect any h
39Executing the Test:♦ To execute the manual check press the button for about five seconds until the UPS acoustic signal fades out.♦ Additionally the
4Claims in connection with supplied goods must be submitted within eight days of receipt, along with the packing slip. Subsequent claims cann
405.6.2 Computer interfaces RS232 and USBThe UPS offers various interfaces to manage the system and to comfortable readout state information and
41In combination with the intelligent UPS the software ensures high availability of all IT components and full data integrity.The shutdown software “C
426 Signalling and failure solution6.1 LED display1. Main switch of the UPS (mains switch)2. Push button for manually triggering the system test or sw
43is providing battery power to your equipment. On the other hand, the LED indicator gives you a warning which will flash every two seconds wh
446.2 Audible Alarm Trouble Shooting:Problem Cause SolutionSounding every 4 secondsThe UPS is on battery Check the input voltage, the input fuse resp
45Output fuse it releasedCheck the output fuse (B. 3000)UPS could not provide power to the load UPS output recognizes overload or short circuitCheck t
467 MaintenanceThe PROTECT B. consists of advanced and resistant components. To guarantee a continuous and high availability it is recommended t
47Fan controlThe fan has to be checked on a regular basis for dustintrusion and strange untypical sounds. Clogged ventilation has to
48PROTECT B. 750 and B.10001. Unscrew the two screws on the side and remove the front panel carefully on both ends. Make sure that the panel
495. Close and reinstall the front panel. Take care to push it in firmly and fix the front panel with the two screws from the beginning. PROTECT B. 15
5Table of Contents1 Notes on these Operating Instructions...32 System Description ...
503. Withdraw the new batteries from the transport container and put into the right position. Fix both blocks together and connect the el
513. Pull first the right battery out and then the left one.4. Withdraw the new batteries from the transport container and put into the rig
528 Storage, Dismantling and DisposalStorageLong storage times without charging or discharging the battery at regular intervals may lead to
539 Glossary9.1 Technical termsAVR Automatic Voltage Regulationagainst mains voltage variationsDC/DC Booster Circuit technology to boost the direct vo
54Guarantee certificateType: …….…………………...Serial-no.: ……………………..……………...
65.6 Interfaces and communication...395.6.1 Data line protection RJ11 and RJ45 (modem / telephone / fax / network)...
72 System DescriptioniPROTECT B. is an Uninterruptible Power Supply (UPS) for essential loads such as PCs, workstations, servers, networ
8♦ Micro processor control for high availability, suited for generator mode♦ Easy extension of battery capacity using external batteries (starting wit
9stabilizes the load voltage. As a result, voltage fluctuations in the public utility's mains are reduced to a level which is acceptabl