ENGINEERING SPECIFICATIONENProtect 2.33 2.0UninterruptiblePower Supply UPS
10Specification DescriptionOverload warning• Load on any phase higher than 100% rated kVA per phase (Sunit (kVA) / 3).• Total load on all 3 phases
11Specification DescriptionInverter current limitDefault values:• RMS Limit: 150%• Peak Limit: 300%Both values are programmable through control pan
12 1 min 5 min 10 min150 % 135 % 125 % 100 % Load (%) Time (mins.) OUTPUT TRANSFER TO
13Specification DescriptionBypass voltage margins, bypass failure+12% / -17% (default values)Programmable through control panel. • Maximum upper lim
14Specification DescriptionBypass frequency limits calculationIf bypass frequency is above upper loss limit or below lower loss limit, it is considered
152.4 MAINTENANCE BYPASSSpecification DescriptionMaintenance bypass topology3 phases, Neutral Connects directly the input terminals to the output termi
162.5 BATTERIESSpecification DescriptionBattery number31+31 3 poles: positive, mid-point, negativeBattery type 12 V, lead acid Different capacity depen
17Specification DescriptionPower supply cut-off after end of back-up time11.5 V / battery After cut-off battery voltage and unit shut-down, battery vol
18BATTERY ELECTRICAL SPECIFICATION DEPENDING ON THE MODELNominal rating (kVA) 10 15 20 30 40 60 80Built-in batteries Type 12 V7 Ah12 V7 Ah12 V9 Ah 12
192.6 GENERAL FEATURES & EFFICIENCYSpecification DescriptionUnit power factor 0.8Load power factor range0.1 inductive ~ 0.1 capacitiveThis load po
2CONTENTS1. Description of the unit ... 32. Electrical and performance features ..
202.7 MISCELLANEOUSSpecification DescriptionControl panel 1) LCD display.2) LED indications.3) Keyboard.1) 5,7" LCD touchscreen, backlight (wit
21Specification DescriptionFan speed control1) Slow (less noisy)2) FastFan speed is slow (half-speed), while both rectifier and inverter heat sink tempe
222.8 ENVIRONMENTAL PERFORMANCESpecification DescriptionOperating temperature range0 °C ~ 40 °C Normal mode, full load.Storage temperature -15 °C ~ 60
233. PHYSICAL DIMMENSIONS AND MODELSDIMENSIONS & WEIGHTSNominal rating (kVA) (MODELS)10 15 20 30 40 60 80Depth (mm) 700 805Width (mm) 450 590Heigh
GUARANTEEDEALER STAMP/SIGNATUREERRORS AND TECHNICAL MODIFICATION SUBJECT TO CHANGE.OPERATING INSTRUCTIONS8000032013 BAL, ENMODEL:SERIAL NUMBER:PURCHAS
31. DESCRIPTION OF THE UNITThis unit is an on-line, double conversion, three-phase uninterruptible power supply.The classification of this unit, accord
42. ELECTRICAL AND PERFORMANCE FEATURES2.1 MAINS INPUT (RECTIFIER INPUT LINE)Specification DescriptionInput topology3 phases, Neutral + GroundNominal i
5Specification DescriptionFrequency limits calculationIf input frequency is above upper loss limit or below lower loss limit, it is considered as a mai
6Specification DescriptionInput Protection• Units 10 ~ 30 kVA: 3-phase Circuit Breaker used as switch and current protection.• Units 40 ~ 80 kVA:
72.2 INVERTERSpecification DescriptionInverter topology3 phases, NeutralNominal inverter voltage3 x 400 V ph-ph, 230 V ph-NInverter voltage accuracy±0.
8Output dynamic performance classification“111” Output dynamic performance classifi-cation “1” (see EN-62040-3) in either:a) Change of operation mode; b
9Inverter frequency accuracy without mains±0.05%Max. synchroniza-tion speed10 Hz / s (default value) Programmable through control panel, from 0.1 H